Concrete Roof Decks Have Several Advantages Over Their Steel Counterparts

By Thomas J Taylor

March 22, 2018

Concrete decks

Concrete decks are one of the more common types of low-slope roof decks for commercial buildings. Steel and wood roof decks are the other most common types. Concrete roof decks make up approximately 13-14% of the new and retrofit low-slope construction market, according to the National Roofing Contractors Association (NRCA) 2015-2016 Market Survey. This article examines the advantages of concrete roof decks, the various types, and some of the precautions that should be taken to ensure success.

Advantages of Concrete Decks

While there are many advantages to concrete decks, there are two primary reasons to consider them. These are based on desired fire ratings and structural requirements.

Concrete can have a wide range of densities depending on the type and amount of aggregate used, the amount of water used in the mixture, and whether air is introduced as a foam via the use of surfactants and the like. Concrete for roofing applications generally fits into one of several categories, depending on the requirements. The properties of each type cover a range depending on the raw materials. The following table shows density ranges followed by typical property values that can be expected.

Chart
* Values for the concrete structural board are estimates based on the published density.

Designers and specifiers should always note that actual property values will depend on aggregate type and source, the volume of water used, and other raw material factors. Always consult with local suppliers to ensure requirements are met.

When concrete is used as a structural component, designers typically specify the compressive strength. This is only loosely related to the compressive strength of the coarse aggregate and the American Concrete Institute (ACI) 213R-03 reports that for typical building-slab compressive strengths – up to about 5,000 psi – "there is no reliable correlation between aggregate strength and concrete strength."

There are five general types of concrete roof deck, as follows.

Structural Concrete Decks

These are cast-in-place and become an integral part of the structure. They use normal weight concrete and are designed to carry heavy loads. Foam insulation such as polyiso can be adhered on top, followed by the roof membrane. Also, the structural roof deck can be insulated with poured in-place lightweight insulating concrete with the roof membrane installed on top.

Structural Concrete Composite Deck

These are based on a steel panel deck system that is overlaid with normal weight or lightweight structural concrete. Loads are carried by the combination of the steel deck and concrete, which act as a single component. Typically, the steel panels are embossed to ensure mechanical coupling to the concrete. Like structural concrete roof decks, composite decks are normally insulated using adhered foam insulation panels or poured-in-place lightweight insulating concrete.

Lightweight Insulating Concrete Decks

Lightweight insulating concrete (LWIC) can be poured over a variety of structural deck systems that have been designed to carry loads. These can be either of the two structural concrete deck types already described or a structural steel deck. While published properties of LWIC are based on the use of lightweight aggregates or foamed concrete, LWIC can also incorporate foam boards. The following picture shows lightweight insulating concrete being poured over boards that have been set into a thin layer of LWIC.


Siplast Insulating Concrete

When this is done, the concrete completely encapsulates the foam, which is frequently expanded polystyrene. The picture is of a Siplast system, and the resulting structure is shown here:

By arranging boards of different thicknesses, combined with smoothing of the surface, a positive pitch can be achieved to allow for good drainage.

Precast Concrete Decks

There are a number of types but usually, the precast members are comprised of reinforced, pre-stressed or post tensioned normal weight concrete. They can be T-shaped or hollow form planks. The precast assembly is normally covered with a layer of poured lightweight insulating or structural lightweight concrete, which serves as a leveling layer. Because the precast planks are usually covered with a poured concrete, they are considered as equivalent to poured structural decks for the purposes of this article. As with the previous types, the roof is completed with adhered foam insulation and a membrane.

Structural Concrete Boards

These are relatively thin (typically ¾ inch) factory formed boards that are screwed down onto a structural steel support (e.g., "C" channels). Conceptually, they can be thought of as being similar to steel deck panels that are installed over steel joists, but offering greater fire protection. Insulation can be mechanically attached or adhered, followed by application of the membrane.

Advantages of Poured Concrete Decks

Whether they are structural or insulating, poured-in-place concrete decks have a number of advantages.

  • Fire ratings: In accordance with ASTM E119, Standard Methods of Fire Tests of Building Construction and Materials, the American National Standards Institute (ANSI) and Underwriters Laboratories (UL) list minimum concrete thicknesses required for various fire ratings. The following table is summarized from ANSI/UL 263 Design No. J718.

As the density decreases so does the thermal conductivity and hence the fire rating is improved. However, as density decreases so does the compressive strength.

  • Wind uplift ratings: As wind rises up and over a building, it creates uplift pressure that exerts an upwards force on roof membranes. By greatly restricting air flow up into a roof assembly, the resistance to that upwards force is increased. Poured concrete decks can be effectively sealed at penetrations and roof edges and greatly reduce the amount of air that can penetrate upwards. This is shown in the following schematic comparing a poured concrete deck with a steel deck.

There are two main reasons why concrete decks can potentially improve wind uplift resistance, depending on concrete specification and overall roof assembly design. First, fasteners in structural concrete have a much higher pull-out strength compared to steel. With #14 fasteners for example, it's by a factor of over 2:1. Second, a steel deck system that has an adhered membrane and mechanically attached insulation can be ultimately limited by the fastener pull-out strength. This tends to limit the wind uplift resistance for roofs with steel decks to approximately 1-180 psf in 12x24 wind uplift testing. However, fully adhered structural concrete deck systems have achieved 1-300 psf or higher in similar testing.

Even though wind uplift resistance is often discussed in terms of wind speeds, the actual cause of roof wind uplift is slightly more complex. Roof damage caused by wind occurs when the air pressure below the roofing assembly is greater than the air pressure above the building's roof. As wind flows over the building, the pressure directly above the surface of the roof decreases. At the same time, internal air pressure increases due to air infiltration through openings, cracks, etc. The result is a net upward force on the roofing system. While concrete decks, when installed properly, can greatly reduce internal air flow into a roof assembly, if penetrations through a concrete deck are made later, these must be carefully sealed to prevent upwards air movement.

Air barrier: The International Energy Conservation Code (IECC) considers concrete in the following forms to be an effective air barrier, provided that all seams and joints are sealed.

  • Cement board having a thickness of not less than 1/2 inch (12 mm).

  • A Portland cement/sand parge, or gypsum plaster having a thickness of not less than 5/8 inch (16 mm).

  • Cast-in-place and precast concrete.

As noted previously, poured concrete decks effectively seal around penetrations. However, with any concrete deck, it's important to carefully consider the roof to wall termination and ensure that all gaps are closed up and sealed.

  • Thermal mass: Improvements in the energy efficiency of buildings are commonly achieved through increased thermal insulation. In fact, most model codes use thermal insulation as the only method of improving energy efficiency of building enclosures. However, there are many indications that thermal mass could also offer a means to both improve occupant comfort and lower energy use. Thermal mass affects the dynamic flow of heat into and out of buildings but has not received as much attention as thermal resistance for improving the energy efficiency of building enclosures. Concrete can add significant thermal mass to an assembly. That thermal mass could help to dampen interior temperature swings and thereby improve occupants' comfort. Also, it can dampen and delay heat fluxes caused by the sun, moving peak heat flux from the mid-day to later in the evening. This could help improve energy efficiency especially for buildings only occupied during daytime hours.

  • Ability to Add Slope: A slope can be added to a poured concrete deck during installation. This was discussed in the LWIC section earlier. By achieving a positive pitch with the concrete, it is possible to eliminate the need for tapered foam insulation while enabling drainage.

Disadvantages of Poured Concrete Decks

  • Weight: Roof designers need to consider the added weight introduced by concrete decks. It is important to understand the weight of locally sourced concrete versus simply relying on data from national handbooks. Always consult with a structural engineer. An advantage of structural concrete boards is that the added weight is lower than for poured concrete. However, concrete boards then require careful sealing at joints and penetrations to reduce air movement up into the assembly.

  • Water content: Roof decks that are cast-in-place contain a high level of water when poured. This is true for normal weight structural concrete and, importantly, the amount of water is greatly increased with the use of lightweight structural concrete. Normal weight structural concrete uses regular aggregates (i.e., hard rocks) with a low moisture absorption rate, while lightweight concrete uses shales and clays that are expanded with air to make them less dense but they have a higher moisture absorption rate.

On a job site, regardless of concrete type, additional water is often added to the mix to reduce the viscosity to ensure concrete easily flows so there are no gaps or voids in the final product. Aggregate for lightweight concrete is often intentionally loaded with water because of the voids. This is necessary so the water needed for concrete curing is not pulled into the aggregate.

Typically the roofing industry has required a 28‐day curing period prior to testing the roof deck for "dryness" and suitability for roofing. This recommendation was garnered from the concrete industry's recommendation for the appropriate amount of time for concrete to cure and develop adequate compressive strength; however, the 28-day time frame is not related to the amount of water in the concrete, only to the cure time. The roofing industry now understands that concrete continues to cure and release excess moisture (i.e., dry out) for a significant time. It's important to note that lightweight concrete's higher moisture content (relative to normal weight) means a much longer drying time is needed.

When a concrete deck is poured, some of the mix water is used up by the curing process, and some evaporates; but the rate of evaporation is slow, so large quantities of water remain stored within the structure of the concrete for extended periods of time. Moisture retention is exacerbated by construction methods that install concrete over non‐removable non-vented metal forms (or other impermeable substrates). While the concrete itself is generally not damaged by this moisture, the moisture typically migrates into the roofing system where it is absorbed by materials that are more sensitive to moisture.

There are several technical advisories that have been issued to raise awareness about the potential for moisture issues associated with concrete roof decks. These include the National Roofing Contractors Association, the Asphalt Roofing Manufacturers Association, the Single-Ply Roofing Institute, the Polyisocyanurate Insulation Manufacturers Association, and the International Institute of Building Enclosure Consultants.

Allowing concrete to thoroughly dry is most appropriate; however, it is reasonably impractical to go beyond 28 days. So more realistic ideas must be implemented to accommodate a potentially substrate; those follow.

  • Installation of a vapor retarder on the top surface of the concrete deck. The Midwest Roofing Contractors Association (MRCA) advises that a vapor retarder of less than 0.01 perm is necessary over new concrete roof decks. From a practical standpoint, a vapor retarder of less than 0.01 perm is effectively a vapor barrier—almost no moisture passes through into the roof assembly. For more on the use of vapor retarders see this guide.

There are three classes of vapor retarders/barriers: Class I, II, and III. Each has a varying permeability rating. A Class I vapor retarder has a perm rating of 0.01 to 0.1; a Class II vapor retarder has a perm rating of 0.1 to 1.0; and a Class III vapor retarder has a perm rating of 1 to 10. MRCA is advising to use a better-than-Class 1 vapor retarder over new concrete roof decks because of its ability to prevent moisture from entering the roof system.

Although industry guidance points towards the use of a vapor retarder over concrete decks, designers must consider the potential issues with installing a roofing system with a double vapor barrier. Moisture that gets in between the roof membrane and the vapor retarder at the roof deck is essentially trapped.

  • Use a venting base sheet in conjunction with vents and venting edge details (at edges, parapets and penetrations) to provide a pathway to allow the moisture in a wet concrete deck to escape slowly over time.

  • Lightweight concrete should always be installed over a vented steel deck to allow downward drying.

For more information about moisture in concrete decks see this article by Kirby.

Advantages and Disadvantages of Structural Concrete Boards

  • Structural concrete boards improve the fire resistance of roof assemblies but, due to their relatively low thickness, do not offer the same fire resistance as poured concrete decks.

  • Concrete boards are factory cured and therefore do not have the moisture issues associated with poured concrete decks.

  • Concrete boards are similar to steel roof deck panels in that they do not prevent air and moisture from migrating up into the roof assembly. The following schematic shows that such systems can be "enhanced" by sealing around penetrations and applying a self-adhering vapor retarder to the concrete board deck.

Adhering the vapor retarder directly to the concrete deck ensures that it is below the dew point so long as a code-required level of insulation is installed above the vapor retarder. A good example of such a product is GAF's SA Vapor Retarder. For most vapor retarders, application direct to a steel deck doesn't meet many fire codes. Concrete boards can provide a good substrate for the application of the vapor retarder while also improving fire performance.

Conclusions

Concrete decks have a number of advantages over steel decks. These include improved fire ratings and wind uplift ratings. Also, concrete is classified by the IECC as an air barrier provided that seams and joints are sealed.

Care must be taken to ensure that moisture in poured concrete decks is prevented from moving upwards into the roof assembly. This is typically achieved by the installation of a vapor retarder over the deck.

Structural concrete panels are factory cured and can be a good substrate for self-adhered vapor retarders when there is a risk of moisture migration from within the building up into the roof assembly.

About the Author

Thomas J Taylor, PhD is the Building & Roofing Science Advisor for GAF. Tom has over 20 year’s experience in the building products industry, all working for manufacturing organizations. He received his PhD in chemistry from the University of Salford, England, and holds approximately 35 patents. Tom’s main focus at GAF is roofing system design and building energy use reduction. Under Tom’s guidance GAF has developed TPO with unmatched weathering resistance.

Related Articles

Roofers install a GAF EverGuard PVC roofing system.
Commercial Roofing

How PVC Experts Can Help Design Specialized Roofing Projects

With the growing popularity and versatility of PVC roofing systems, GAF has responded by building a team of PVC experts to aid architects, specifiers, and the design community in project success. These highly trained and experienced professionals offer 1:1 support to help answer customers' questions and unique needs when working with PVC on roofing projects, and are here to help you!PVC, or polyvinyl chloride, is a single-ply thermoplastic roofing membrane. The material's characteristics help it thrive in particularly challenging applications. In fact, PVC roofing systems have a proven track record in the US, first introduced in the 1970s after making their debut in Germany a decade earlier.Here's a look at the benefits of PVC roofing systems as well as the guidance and support offered by the PVC experts at GAF.PVC Roofing Advantages and ApplicationsWhile several materials are available for use in roofing systems, PVC has been identified as a particularly long-lasting option. Accordingly, it's steadily grown in popularity nationwide.David Allor, senior area PVC specialist, joined the GAF team in 2022 as a PVC expert. His role was created specifically to support roof designers. Allor has an extensive background in the commercial roofing industry and extensive knowledge about PVC as a high-performance roofing solution."The industry refers to it as a very spec-driven product, and I believe what they're speaking to is a specifier's preference to work with a product that's been well established in the market and field tested," Allor shares. "It has the ability to provide protection against chemical exposure* and stand up well to challenging environments."While PVC may be a spec-driven product, it's also application-driven. Allor explains that PVC roofs may help provide protection for restaurants, food manufacturers, and packaging plants—any facility using animal fats where oils may be exhausted.* He also says that even if the building itself isn't exhausting gases, grease, or chemicals, it's important to consider the buildings and structures that surround it, as their exteriors may be subjected to exhaust that could degrade roofing systems.*Supporting the Design CommunityAs North America's largest roofing materials manufacturer, GAF has equipped teams with the resources and specialists needed to supply customers with more than just products. In recent years, the company built a solid team of PVC specialists that cover the entire US. These specialists assist customers with PVC specifications, roof system designs, and whatever else designers need to ensure successful project outcomes.Whether your project or design firm is based in the Northeast, Southeast, Southwest, Midwest, or West Coast, a PVC specialist is positioned to help. Allor explains the team of GAF PVC specialists is active in the organizations specifiers belong to, including the American Institute of Architects, the Construction Specifications Institute, and the International Institute of Building Enclosure Consultants.Allor describes the team's role as supporting the customer and connecting them to other GAF project support teams that can help. For instance, he said he called on a leading architectural design firm in the Boston area—and two months later, someone reached out for assistance with a specific project needing a tight turnaround."Literally within 12 hours of them reaching out to us, we replied and committed to three pertinent deliverables, those being a Tapered ISO Design Package, an Assembly Letter confirming all FM Requirements, and last but not least, a conference call the next day with the Building and Roofing Science team to go over three critical transitional details." Allor says.Committing to Successful Project OutcomesThe PVC specialists at GAF are focused on one goal: helping architects, specifiers, and the roofing design community achieve successful project outcomes through a high-performing PVC roofing system. With professionals like Allor providing insight and guidance, you can rest assured your PVC project will be in good hands.Ready to get started on your next PVC roofing project? Explore the different PVC roofing solutions available, and visit this page to find your local PVC roofing specialist who is ready to assist you.*GAF warranties and guarantees do not provide coverage against exposure to chemicals, grease, oils, animal fats or exhaust. Refer to gaf.com for more information on warranty and guarantee coverage and restrictions.

By Authors Karen L Edwards

April 22, 2024

An aerial shot of the student housing building on the Texas A&M campus.
Building Science

Are Hybrid Roof Assemblies Worth the Hype?

How can roofing assemblies contribute to a building's energy efficiency, resiliency, and sustainability goals? Intentional material selection will increase the robustness of the assembly including the ability to weather a storm, adequate insulation will assist in maintaining interior temperatures and help save energy, and more durable materials may last longer, resulting in less frequent replacements. Hybrid roof assemblies are the latest roofing trend aimed at contributing to these goals, but is all the hype worth it?What is a hybrid roof assembly?A hybrid roof assembly is where two roofing membranes, composed of different technologies, are used in one roof system. One such assembly is where the base layers consist of asphaltic modified bitumen, and the cap layer is a reflective single-ply membrane such as a fleece-back TPO or PVC. Each roof membrane is chosen for their strengths, and together, the system combines the best of both membranes. A hybrid system such as this has increased robustness, with effectively two plies or more of membrane.Asphaltic membranes, used as the first layer, provide redundancy and protection against punctures as it adds overall thickness to the system. Asphaltic systems, while having decades of successful roof installations, without a granular surface may be vulnerable to UV exposure, have minimal resistance to ponding water or certain chemical contaminants, and are generally darker in color options as compared to single ply surfacing colors choices. The addition of a single-ply white reflective membrane will offset these properties, including decreasing the roof surface temperatures and potentially reducing the building's heat island effect as they are commonly white or light in color. PVC and KEE membranes may also provide protection where exposure to chemicals is a concern and generally hold up well in ponding water conditions. The combination of an asphaltic base below a single-ply system increases overall system thickness and provides protection against punctures, which are primary concerns with single-ply applications.Pictured Above: EverGuard® TPO 60‑mil Fleece‑Back MembraneOlyBond 500™ AdhesiveRUBEROID® Mop Smooth MembraneMillennium Hurricane Force ® 1-Part Membrane AdhesiveDensDeck® Roof BoardMillennium Hurricane Force ® 1-Part Membrane AdhesiveEnergyGuard™ Polyiso InsulationMillennium Hurricane Force ® 1-Part Membrane AdhesiveConcrete DeckPictured Above: EverGuard® TPO 60‑mil Fleece‑Back MembraneGAF LRF Adhesive XF (Splatter)RUBEROID® HW Smooth MembraneDrill‑Tec™ Fasteners & PlatesDensDeck® Prime Gypsum BoardEnergyGuard™ Polyiso InsulationEnergyGuard™ Polyiso InsulationGAF SA Vapor Retarder XLMetal DeckWhere are hybrid roof assemblies typically utilized?Hybrid roof assemblies are a common choice for K-12 & higher education buildings, data centers, and hospitals due to their strong protection against leaks and multi-ply system redundancy. The redundancy of the two membrane layers provides a secondary protection against leaks if the single-ply membrane is breached. Additionally, the reflective single-ply membrane can result in lower rooftop temperatures. The addition of a reflective membrane over a dark-colored asphaltic membrane will greatly increase the Solar Reflectance Index (SRI) of the roof surface. SRI is an indicator of the ability of a surface to return solar energy into the atmosphere. In general, roof material surfaces with a higher SRI will be cooler than a surface with a lower SRI under the same solar energy exposure. A lower roof surface temperature can result in less heat being absorbed into the building interior during the summer months.Is a hybrid only for new construction?The advantage of a hybrid roof assembly is significant in recover scenarios where there is an existing-modified bitumen or built-up roof that is in overall fair condition and with little underlying moisture present. A single ply membrane can be installed on top of the existing roof system without an expensive and disruptive tear-off of the existing assembly. The addition of the single-ply membrane adds reflectivity to the existing darker colored membrane and increases the service life of the roof assembly due to the additional layer of UV protection. Additionally, the single-ply membrane can be installed with low VOC options that can have minimum odor and noise disturbance if construction is taking place while the building is occupied.Is the hybrid assembly hype worth it?Absolutely! The possibility to combine the best aspects of multiple roofing technologies makes a hybrid roof assembly worth the hype. It provides the best aspects of a single-ply membrane including a reflective surface for improved energy efficiency, and increased protection against chemical exposure and ponding water, while the asphaltic base increases overall system waterproofing redundancy, durability and protection. The ability to be used in both new construction and recover scenarios makes a multi-ply hybrid roof an assembly choice that is here to stay.Interested in learning more about designing school rooftops? Check out available design resources school roof design resources here. And as always, feel free to reach out to the Building & Roofing Science team with questions.This article was written by Kristin M. Westover, P.E., LEED AP O+M, Technical Manager, Specialty Installations, in partnership with Benjamin Runyan, Sr. Product Manager - Asphalt Systems.

By Authors Kristin Westover

December 28, 2023

Flat roof with hot air welded pvc membrane waterproofing for ballasted system
Building Science

Thermal Bridging Through Roof Fasteners: Why the Industry Should Take Note

What is going on here?No, this roof does not have measles, it has a problem with thermal bridging through the roof fasteners holding its components in place, and this problem is not one to be ignored.As building construction evolves, you'd think these tiny breaches through the insulating layers of the assembly, known as point thermal bridges, would matter less and less. But, as it happens, the reverse is true! The tighter and better-insulated a building, the bigger the difference all of the weak points, in its thermal enclosure, make. A range of codes and standards are beginning to address this problem, though it's important to note that there is often a time lag between development of codes and their widespread adoption.What Is the Industry Doing About It?Long in the business of supporting high-performance building enclosures, Phius (Passive House Institute US) provides a Fastener Correction Calculator along with a way to calculate the effect of linear thermal bridges (think shelf angles, lintels, and so on). By contrast, the 2021 International Energy Conservation Code also addresses thermal bridging, but only considers framing materials to be thermal bridges, and actually pointedly ignores the effects of point loads like fasteners in its definition of continuous insulation: "insulation material that is continuous across all structural members without thermal bridges other than fasteners and service openings" (Section C202). Likewise, The National Energy Code of Canada for Buildings: 2020 addresses thermal bridging of a number of building components, but also explicitly excludes fasteners: "in calculating the overall thermal transmittance of assemblies…fasteners need not be taken into account" (Section 3.1.1.7.3). Admittedly, point thermal bridges are often excluded because it is challenging to assess them with simple simulation tools.Despite this, researchers have had a hunch for decades that thermal bridging through the multitude of fasteners often used in roofs is in fact significant enough to warrant study. Investigators at the National Bureau of Standards, Oak Ridge National Laboratory, the National Research Council Canada, and consulting firms Morrison Hershfield and Simpson Gumpertz & Heger (SGH), have conducted laboratory and computer simulation studies to analyze the effects of point thermal bridges.Why Pay Attention Now?The problem has been made worse in recent years because changes in wind speeds, design wind pressures, and roof zones as dictated by ASCE 7-16 and 7-22 (see blogs by Jim Kirby and Kristin Westover for more insight), mean that fastener patterns are becoming denser in many cases. This means that there is more metal on average, per square foot of roof, than ever before. More metal means that more heat escapes the building in winter and enters the building in summer. By making our buildings more robust against wind uplift to meet updated standards, we are in effect making them less robust against the negative effects of hot and cold weather conditions.So, how bad is this problem, and what's a roof designer to do about it? A team of researchers at SGH, Virginia Tech, and GAF set out to determine the answer, first by simplifying the problem. Our plan was to develop computer simulations to accurately anticipate the thermal bridging effects of fasteners based on their characteristics and the characteristics of the roof assemblies in which they are used. In other words, we broke the problem down into parts, so we could know how each part affects the problem as a whole. We also wanted to carefully check the assumptions underlying our computer simulation and ensure that our results matched up with what we were finding in the lab. The full paper describing our work was delivered at the 2023 IIBEC Convention and Trade Show, but here are the high points, starting with how we set up the study.First, we began with a simple 4" polyisocyanurate board (ISO), and called it Case A-I.Next, we added a high-density polyisocyanurate cover board (HD ISO), and called that Case A-II.Third, we added galvanized steel deck to the 4" polyiso, and called that Case A-III.Finally, we created the whole sandwich: HD ISO and ISO over steel deck, which was Case A-IV.Note that we did not include a roof membrane, substrate board, air barrier, or vapor retarder in these assemblies, partly to keep it simple, and partly because these components don't typically add much insulation value to a roof assembly.The cases can be considered base cases, as they do not yet contain a fastener. We needed to simulate and physically test these, so we could understand the effect that fasteners have when added to them.We also ran a set of samples, B-I through B-IV, that corresponded with cases A-I through A-IV above, but had one #12 fastener, 6" long, in the center of the 2' x 2' assembly, with a 3" diameter insulation plate. These are depicted below. The fastener penetrated the ISO and steel deck, but not the HD ISO.One visualization of the computer simulation is shown here, for Case B-IV. The stripes of color, or isotherms, show the vulnerability of the assembly at the location of the fastener.What did we find? The results might surprise you.First, it's no surprise that the fastener reduced the R-value of the 2' x 2' sample of ISO alone by 4.2% in the physical sample, and 3.4% in the computer simulation (Case B-I compared to Case A-I).When the HD ISO was added (Cases II), R-value fell by 2.2% and 2.7% for the physical experiment and computer simulation, respectively, when the fastener was added. In other words, adding the fastener still caused a drop in R-value, but that drop was considerably less than when no cover board was used. This proved what we suspected, that the HD ISO had an important protective effect against the thermal bridging caused by the fastener.Next, we found that the steel deck made a big difference as well. In the physical experiment, the air contained in the flutes of the steel deck added to the R-value of the assembly, while the computer simulation did not account for this effect. That's an item that needs to be addressed in the next phase of research. Despite this anomaly, both approaches showed the same thing: steel deck acts like a radiator, exacerbating the effect of the fastener. In the assemblies with just ISO and steel deck (Cases III), adding a fastener resulted in an R-value drop of 11.0% for the physical experiment and 4.6% for the computer simulation compared to the assembly with no fastener.Finally, the assemblies with all the components (HD ISO, ISO and steel deck, a.k.a. Cases IV) showed again that the HD ISO insulated the fastener and reduced its negative impact on the R-value of the overall assembly. The physical experiment had a 6.1% drop (down from 11% with no cover board!) and the computer simulation a 4.2% drop (down from 4.6% with no cover board) in R-value when the fastener was added.What Does This Study Tell Us?The morals of the study just described are these:Roof fasteners have a measurable impact on the R-value of roof insulation.High-density polyisocyanurate cover boards go a long way toward minimizing the thermal impacts of roof fasteners.Steel deck, due to its high conductivity, acts as a radiator, amplifying the thermal bridging effect of fasteners.What Should We Do About It?As for figuring out what to do about it, this study and others first need to be extended to the real world, and that means making assumptions about parameters like the siting of the building, the roof fastener densities required, and the roof assembly type.Several groups have made this leap from looking at point thermal bridges to what they mean for a roof's overall performance. The following example was explored in a paper by Taylor, Willits, Hartwig and Kirby, presented at the RCI, Inc. Building Envelope Technology Symposium in 2018. In that paper, the authors extended computer simulation results from a 2015 paper by Olson, Saldanha, and Hsu to a set of actual roofing scenarios. They found that the installation method has a big impact on the in-service R-value of the roof.They assumed a 15,000-square-foot roof, fastener patterns and densities based on a wind uplift requirement of 120 pounds per square foot, and a design R-value of R-30. In this example, a traditional mechanically attached roof had an in-service R-value of only R-25, which is a 17% loss compared to the design R-value.An induction-welded roof was a slight improvement over the mechanically attached assembly, with an in-service value of only R-26.5 (a 12% loss compared to the design R-value).Adhering instead of fastening the top layer of polyiso resulted in an in-service R-value of R-28.7 (a 4% loss compared to the design R-value).Finally, in their study, an HD polyiso board was used as a mechanically fastened substrate board on top of the steel deck, allowing both layers of continuous polyiso insulation and the roof membrane to be adhered. Doing so resulted in an in-service R-value of R-29.5, representing only a 1.5% loss compared to the design R-value.To operationalize these findings in your own roofing design projects, consider the following approaches:Consider eliminating roof fasteners altogether, or burying them beneath one or more layers of insulation. Multiple studies have shown that placing fastener heads and plates beneath a cover board, or, better yet, beneath one or two layers of staggered insulation, such as GAF's EnergyGuard™ Polyiso Insulation, can dampen the thermal bridging effects of fasteners. Adhering all or some of the layers of a roof assembly minimizes unwanted thermal outcomes.Consider using an insulating cover board, such as GAF's EnergyGuard™ HD or EnergyGuard™ HD Plus Polyiso cover board. Installing an adhered cover board in general is good roofing practice for a host of reasons: they provide enhanced longevity and system performance by protecting roof membranes and insulation from hail damage; they allow for enhanced wind uplift and improved aesthetics; and they offer additional R-value and mitigate thermal bridging as shown in our recent study.Consider using an induction-welded system that minimizes the number of total roof fasteners by dictating an even spacing of insulation fasteners. The special plates of these fasteners are then welded to the underside of the roof membrane using an induction heat tool. This process eliminates the need for additional membrane fasteners.Consider beefing up the R-value of the roof insulation. If fasteners diminish the actual thermal performance of roof insulation, building owners are not getting the benefit of the design R-value. Extra insulation beyond the code minimum can be specified to make up the difference.Where Do We Go From Here?Some work remains to be done before we have a computer simulation that more closely aligns with physical experiments on identical assemblies. But, the two methods in our recent study aligned within a range of 0.8 to 6.7%, which indicates that we are making progress. With ever-better modeling methods, designers should soon be able to predict the impact of fasteners rather than ignoring it and hoping for the best.Once we, as a roofing industry, have these detailed computer simulation tools in place, we can include the findings from these tools in codes and standards. These can be used by those who don't have the time or resources to model roof assemblies using a lab or sophisticated modeling software. With easy-to-use resources quantifying thermal bridging through roof fasteners, roof designers will no longer be putting building owners at risk of wasting energy, or, even worse, of experiencing condensation problems due to under-insulated roof assemblies. Designers will have a much better picture of exactly what the building owner is getting when they specify a roof that includes fasteners, and which of the measures detailed above they might take into consideration to avoid any negative consequences.This research discussed in this blog was conducted with a grant from the RCI-IIBEC Foundation and was presented at IIBEC's 2023 Annual Trade Show and Convention in Houston on March 6. Contact IIBEC at https://iibec.org/ or GAF at BuildingScience@GAF.com for more information.